[security warning station] how to check the electrical hazards, there are pictures of the truth!

安全厂商和企业组织也可以考虑采用互联网上的安全数据库,进而搭建和提供更强大的组织上网行为管理体系,确保员工的上网安全和提升生产力。

隐患01
Hidden danger 01
排查依据:GB/T 13869-2008《用电安全导则》5.2:用电产品应具有符合规定的铭牌或标志,以满足安全、使用和维护的要求。
On the basis of investigation: GB\/T 13869-2008 electrical safety guide 5.2: electric products should be in accordance with the provisions of the nameplate or logo, to meet the safety, use and maintenance requirements.
隐患02
Hidden danger 02
排查依据:GB/T 13869-2008《用电安全导则》6.5:一般环境下,用电产品以及电气线路的周围应留有足够的安全通道和工作空间,且不宜堆放易燃易爆和腐蚀性物品。
On the basis of investigation: GB\/T 13869-2008 electrical safety guide 6.5: the general environment, with around products and electrical lines should be adequate safe access and working space, and should not be piled up flammable and corrosive materials.
隐患03
Hidden danger 03
排查依据:GB/T 13869-2008《用电安全导则》6.5:一般环境下,用电产品以及电气线路的周围应留有足够的安全通道和工作空间,且不宜堆放易燃易爆和腐蚀性物品。
On the basis of investigation: GB\/T 13869-2008 electrical safety guide 6.5: the general environment, with around products and electrical lines should be adequate safe access and working space, and should not be piled up flammable and corrosive materials.
隐患04
Hidden danger 04
排查依据:GB/T 13869-2008《用电安全导则》6.13:保护接地线应采用焊接、压接、螺栓连接或其他可靠方法连接,严禁缠绕或挂钩。
Investigation basis: GB\/T 13869-2008 electrical safety guidelines 6.13: the protection of grounding wire should be welded, crimping, bolt connection or other reliable methods of connection, is strictly prohibited winding or hook.
隐患05
Hidden danger 05
排查依据:GB/T 13869-2008《用电安全导则》6.16:插头和插座应按规定正确接线。
Investigation based on: GB\/T 13869-2008 electrical safety guidelines 6.16: plug and socket should be provided according to the correct wiring.
隐患06
Hidden danger 06
排查依据:GB/T 13869-2008《用电安全导则》7.3:用电产品拆除时,应对原来的电源端做妥善处理,不应使用任何可能带电的导电部门外露。
Investigation basis: GB\/T 13869-2008 electricity safety guidelines 7.3: when the demolition of power products, to deal with the original power supply to properly handle, should not use any possible electrification of the exposed sector.
隐患07
Hidden danger 07
排查依据:DL/T 5162.17-2002《电气装置安装工程质量检验及评定规程》第17部分:电气照明装置施工质量检验 3.0.2:照明配电箱安装强度应牢固。
Investigation basis: DL\/T 5162.17-2002 electrical equipment installation engineering quality inspection and evaluation procedures, the seventeenth part: the construction quality inspection of electrical lighting equipment 3.0.2: lighting distribution box installation strength should be firm.
隐患08
Hidden danger 08
排查依据:DL/T 5162.17-2002《电气装置安装工程质量检验及评定规程》第17部分:电气照明装置施工质量检验3.0.2:照明配电箱(板)内部无干净、无杂物。
On the basis of investigation: DL\/T 5162.17-2002 electric equipment installation engineering quality inspection and evaluation procedures in seventeenth parts: the quality of the electric lighting device construction inspection: 3.0.2 lighting distribution box (board) without internal clean.
隐患09
Hidden danger 09
排查依据:DL/T 5162.17-2002《电气装置安装工程质量检验及评定规程》第17部分:电气照明装置施工质量检验3.0.2:照明配电箱(板)控制回路标识齐全清晰。

为了孩子,安全没有上限,米兔故事机拆解

On the basis of investigation: DL\/T 5162.17-2002 electric equipment installation engineering quality inspection and evaluation procedures in seventeenth parts: the quality of the electric lighting device construction inspection: 3.0.2 lighting distribution box (board) control loop identification is complete and clear.
隐患10
Hidden danger 10
排查依据:GB 50169-2006《电气装置安装工程质量检验及验收规范》3.1.3:接地装置不得与金属管道、建筑物、设备的构建有金属的连接。
Investigation basis: GB 50169-2006 electrical equipment installation engineering quality inspection and acceptance specification 3.1.3: grounding device shall not be connected with the construction of metal pipes, buildings, equipment, metal.
隐患11
Hidden danger 11
排查依据:GB 50054-2011《低压配电设计规范》7.2.1 当导线垂直敷设时,距地面低于1.8m段的导线,应用导管保护。
Investigation basis: GB 50054-2011 low voltage distribution design specification 7.2.1 when the wire is laid vertically, from the ground below the 1.8m section of the wire, the use of catheter protection.
隐患12
Hidden danger 12
排查依据:GB 50054-2011《低压配电设计规范》7.2.7对金属导管、金属槽盒有严重腐蚀的场所,不宜采用金属导管、金属槽盒布线。
Investigation basis: GB 50054-2011 low voltage distribution design specification 7.2.7 metal conduit, metal tank box has a serious corrosion of the place, not the use of metal conduit, metal box wiring.
隐患13
Hidden danger 13
排查依据:GB 50054-2011《低压配电设计规范》7.2.20 金属槽盒引出的线路,导线在引出部分应有防止损伤的措施。
Investigation basis: GB 50054-2011 low voltage distribution design specification 7.2.20 metal tank box leads to the wire, the lead in the part of the measures should be taken to prevent damage.
隐患14
Hidden danger 14

上海软件中心与毕马威签署战略合作协议 联合成立网络安全与信…

排查依据:GB 50054-2011《低压配电设计规范》7.6.8 无铠装的电缆在屋内明敷,水平敷设时,与地面距离不应小于2.5m。
According to the investigation: GB 50054-2011 7.6.8 code for design of low voltage power distribution cable inside the unarmored surface, horizontal laying, and the ground should not less than 2.5m.
隐患15
Hidden danger 15
排查依据:JGJ 16-2008《民用建筑电气设计规范》4.6.2 固定式开关柜靠墙布置时,柜后距离与墙净距离应大于0.05m,侧面与净墙距应大于0.2m。
Investigation basis: JGJ 16-2008 civil building electrical design code 4.6.2 fixed switch cabinet against the wall layout, the distance between the cabinet and the wall should be greater than 0.05m net, the side and the net wall distance should be greater than 0.2m.
中国企业走向全球,国际化人才要接地气,融中西,海外风险与安全基础知识素养要强化:
隐患16
Hidden danger 16
排查依据:JGJ 16-2008《民用建筑电气设计规范》4.6.2 屋内配电装置距顶板的距离不宜小于0.8m;当有梁时,距梁底不宜小于0.6m。
Investigation basis: JGJ 16-2008 civil building electrical design code 4.6.2 indoor distribution device from the roof of the distance shall not be less than 0.8m; when there is beam, from the bottom of the beam shall not be less than 0.6m.
隐患17
Hidden danger 17
排查依据:GB 50303-2002《建筑电气工程质量验收规范》12.2.2 电缆出入电缆沟、竖井、建筑物、柜(盘)、台处以及管子管口处等做密封处理。
On the basis of investigation: GB 50303-2002 building electrical engineering quality inspection standard 12.2.2 cable access cable channel, shaft, building, cabinet (disc), and the pipe orifice and sealing treatment.
隐患18
Hidden danger 18
排查依据:GB 50303-2002《建筑电气工程质量验收规范》12.2.2 电缆敷设排列整齐,水平敷设的电缆,首尾两端、转弯两侧及每隔5~10m处设固定点。
On the basis of investigation: GB 50303-2002 building electrical engineering quality inspection standard 12.2.2 cable laying order, cable laying, horizontal, pendulous turn on both sides and every fixed point is set at 5~10m.
隐患19
Hidden danger 19
排查依据:GB 50303-2002《建筑电气工程质量验收规范》14.1.3 防爆导管不应采用倒扣连接;当连接有困难时,应采用防爆活接头,其接合面应当严密。
Investigation basis: GB 50303-2002 building electrical engineering quality acceptance specification 14.1.3 explosion proof pipe should not use inverted connection; when the connection is difficult, should use explosion-proof joint, the joint surface should be tight.
隐患20
Hidden danger 20
排查依据:GB 50303-2002《建筑电气工程质量验收规范》14.2.5 室内进入落地式柜、台、箱、盘内的导管管口,应高出柜、台、箱、盘的基础面50~80mm。
According to the investigation: 50303-2002 GB catheter orifice of electrical engineering construction quality acceptance into the 14.2.5 indoor floor type cabinet, table, box, tray, should be based out of the closet, table, box, plate surface 50~80mm.
隐患21
Hidden danger 21
排查依据 50054-2011《低压配电设计规范》7.6.9 屋内相同电压的电缆并列明敷时,除敷设在托盘、梯架和槽盒内外,电缆之间的静距离不应小于35mm,且不应小于电缆外径。
The investigation on the basis of 50054-2011 low-voltage power distribution design standard 7.6.9 inside the same voltage cable are laid, in addition to laying in tray ladder and groove inside and outside the box, static distance should not be less than 35mm between cables, and should not be less than the outer diameter of cable.

信息安全管理体系如何落到实处

隐患22

Hidden danger 22
排查依据 50054-2011《低压配电设计规范》7.6.38 电缆通过建筑物和构筑物的基础、散水坡、楼板和穿过墙体等处应穿管保护,穿管的内径不应小于电缆外径的1.5倍.
The investigation on the basis of 50054-2011 low voltage distribution design standard 7.6.38 cable through the buildings and structures of the foundation, apron slope floor and wall should be protected through the tube, through the inside diameter of the tube should not be less than 1.5 times of cable diameter.
隐患23
Hidden danger 23
排查依据 50054-2011《低压配电设计规范》7.2.11 金属导管和金属槽盒敷设时,应与其他管道的平行净距离不小于0.1m。
Investigation based on the 50054-2011 low voltage distribution design specification 7.2.11 metal pipe and metal slot box laying, should be parallel with other pipe net distance of not less than 0.1m.
隐患24
Hidden danger 24
排查依据:GB 50303-2002《建筑电气工程施工质量验收规范》6.1.1 柜、屏、台、箱、盘的金属框架及基础型钢必须接地(PE)或接零(PEN)可靠;装有电器的可开启门,门和框架的接地端子间应用裸编制铜线连接,且有标识。
On the basis of investigation: metal frame and base steel GB 50303-2002 construction of electrical engineering construction quality acceptance 6.1.1 screen, table, cabinet, box, the disc must be grounded (PE) or zero (PEN) can open the door with reliable; electrical appliances, grounding terminals using bare copper wire and the door frame system the identification and.
隐患25
Hidden danger 25
排查依据:GB 50303-2002《建筑电气工程施工质量验收规范》6.1.9 照明箱(盘)内配线整齐,无绞线现象。
Based on the investigation of GB 50303-2002: the construction of electrical engineering construction quality acceptance 6.1.9 according to light (disc) within the wiring is neat, no strand phenomenon.